DIVISION 8 - DOORS AND WINDOWS

SECTION 8300 - AUTOMATIC SWINGING DOORS

PART I - GENERAL

1.01 DESCRIPTION

This section covers commercial/industrial duty automatic swinging doors complete with operator, detection device and all associated hardware necessary for a complete installation.

1.02 RELATED WORK COVERED BY OTHER APPLICABLE SECTIONS OF SPECIFICATION SHALL INCLUDE

Section 8 - Doors and Operators

Section 8 - Finish Hardware

Section 8 - Glazing

Section 15 - Mechanical

Section 16 - Electrical

1.03 QUALITY ASSURANCE

ANSI A156.10 Standard: Provide automatic entrance doors complying with applicable requirements of Power Operated Pedestrian Door Standard.

UL 325: Provide powered door operators complying with UL 325, Electrical Door, Drapery, Gate, Louver and Window Operators and Systems.

Manufacturer's Qualifications: Provide units produced by a firm with not less than five years successful experience in the fabrication of automatic entrance doors of the type required for this project.

Installer's Qualifications: Engage an installer who is an authorized representative of the automatic entrance door manufacturer for both the installation and maintenance of the type of units required for this project.

1.04 SUBMITTALS

A. Product Data: Submit manufacturer's product data and standard details for automatic entrance doors includingÄfabrication, finishing, hardware, operators, accessories, and other components of the work. Include rough-in diagrams, wiring diagrams, parts lists, and maintenance instructions, as well as certified test data, where required.

B. Templates and Diagrams: Furnish templates, diagrams, and other data to fabricators and installers of related work as needed for coordination of automatic entrance installation.

C. Shop Drawings: Submit shop drawings for the fabrication and installation of automatic entrance doors and associated components of the work. Indicate anchors, joint system, expansion provisions, hardware, and other components not included in manufacturers standard data. Include glazing details.

1.05 WARRANTY

Units to be warranted against defect in material and workmanship for a period of one year from the date of installation.

PART II - PRODUCT

2.01 MANUFACTURER

Automatic swing door(s) and operation mechanism(s) shall be of type(s) and size(s) as indicated on plans. They shall be manufactured and furnished as a complete unit by Horton Automatics, a division of Overhead Door Corporation.

2.02 EQUIPMENT

A. PNEUMATIC OPERATOR

Shall be Series 5000 pneumatic, power opened and spring closed. The operator shall be concealed in a 6" x 6", extruded aluminum case with removable cover plate for ease of access. The master control switch shall incorporate an adjustable time delay from 1 to 30 seconds. Braking or checking shall be an integral function of the operator, utilization of controlled exhaust air provides shock-proof deceleration of the moving panel(s). A hold open feature shall be provided. The entire operator shall utilize a 24 VAC low voltage current. The power cylinder includes a piston rod moving in a linear motion that is attached to the patented continuous loop, chain drive pivot assembly. The pivot assembly utilizes two high-quality Fafnir self-aligning bearings that serve as the door pivot assembly. The roller chain shall be #40. This results in linear motion of the air piston assembly being converted to rotary motion in the pivot assembly. It shall be UL listed. The springs for closing power must be accessible for replacement and should not require the exchange of any main assembly or gear box. The addition or deletion of a spring shall allow the closing force to be varied. The operator shall be manually operated and be self closing in a power outage. The operator shall include a switch circuit that will cause the operator to be activated when manually pushed.

Series 5100 operator shall be surface mounted above the door with exposed arm connection to the door.

OPTION:

* Power open, power assist spring closing.

Explosion ProofÄThe electromechanical solenoid valve and electronic control shall be installed within 25 feet of the operator and outside the hazardous area. All activating switches shall be explosion proof using an intrinsically safe current.

OPTION:

The aluminum cover shall have the following finish:

(1) Standard Finish: Caustic etch and anodic oxide treatment to conform to aluminum association standards AA-M12C22A31 (204-R1).

(2) Stock Finish: An integral color hard coat finish dark bronze.

(3) Special Finish: An integral color hard coat finish (specify color).

B. DOOR TYPE

Shall be as shown on drawings and in door schedule.

2.03 CONTROL SWITCHES

Note to Spec writer: Horton Automatics offers several options to activate the door and provide safety protection on the swing side.

A safety zone of a length 5" more than the door width in the open position shall be provided on the swing side of the door to either prevent the door from opening or hold the door in the open position when the area of the swing of the door is occupied.

Provide a complete activating/safety system of the type specified herein as shown on the drawings. (Specify appropriate selection.) Safety System shall be placed on the swing side of the door as described in item (1), (2), or (5).

(1) Series 1600 SwingScan sensor mounted on door (a) concealed in a mid rail in the aluminum/glass door (b) surface mounted to door. The sensor shall be mounted 24" to 30" above floor.

(2) Series 1700 RailScan safety system shall be mounted in the horizontal rail of the guide rail or be wall mounted. To provide complete safety zone coverage, photobeams shall be housed in an aluminum extrusion and shall be located every five inches in the safety zone.

Note to spec writer: This system only works with clear glass doors or single solid doors. Activating Device Item (1) and (2) system shall be activated by a:

(3) Motion detector of pattern suitable for door opening size.

(4) C1260 Push Plate Switch to activate door. Switch placement is shown on drawing. A safety system shall be placed on the swing side of the door as described in item (1), (2), or (5) (specify appropriate selection).

Safety and Activation System

(5) Electric floor mat switch complete with (a) surface (b) recess trim mounted on each side of the door (activating and safety area) or mounted in the safety area.

Note: See catalog section E for more detailed specification of each system.

2.04 GUIDE RAILS

Guide rails are of type selected and shall be provided at the swing side of the door. (Unless a natural wall or separator exists.)

2.05 REQUIREMENTS FOR WORK SPECIFIED IN OTHER AREAS

AIR SUPPLY (select one of the two)

(1) AIR SUPPLY: Shall be furnished and installed by the General Contractor and by means of a complete unit with supply tank, compressor, motor regulator, safety valve and pressure cut-off switch.

(2) AIR SUPPLY: Shall be by use of existing air supply which shall be regulated to approximately 65-75 PSI with 1/2 cubic feet volume per minute available to each operator.

PLUMBING: The General Contractor or Plumbing Contractor shall supply and install the air line to connect the supply tank on the air compressor to the Horton Automatics operator with copper tubing of proper size as recommended by door manufacturers.

Drain traps shall be furnished and installed by Plumbing Contractor at all low points in the air lines. This plumbing shall conform to local plumbing codes. If the air lines are put in the floor slab (not recommended), drain traps shall be installed at all low points in the lines. In areas where air lines are subjected to extreme cold, dehydrating equipment should be specified.

ELECTRICAL: The General Contractor or Electrical Contractor shall furnish and install all wiring to operator and compressor. The compressor shall be provided with 120 or 220 VAC service at 15 AMPS. Each operator shall be provided with 120 VAC service to a 4" x 4" x 1-1/2" square outlet box where a 120/24 VAC-NEC Class II-55VA transformer supplied by Horton Automatics is to be mounted.

GLASS AND GLAZING: Shall be as provided under glass and glazing section of specifications. Glazing must be strictly in accordance with manufacturer's instructions (ANSI Standard Z97.1).

PART III - EXECUTION

3.01 INSPECTION

Assure that frame openings correspond to dimensions of frames furnished. Floor conditions must be suitable for safety and performance. Check that surfaces to contact frames are free of debris. Do not proceed with installation until unsatisfactory conditions are corrected.

3.02 INSTALLATION

Install, plumb, level, true-to-line, and rigidly secure in openings. After applying operators and hardware, adjust to achieve smooth and quiet operation. Install in accordance with approved shop drawings.

3.03 ADJUSTMENT AND CLEANING

A. Remove dirt and excess sealants or glazing compound from exposed surfaces.

B. Adjust moving parts for smooth operation.

C. Remove debris from project site.

END OF SECTION